Answer:
Circuit breakers of type B trip when the current is 3 to 5 times higher than the rated current. Circuit breakers of type C trip when the current is 5 to 10 times higher than the rated current.
Type B breakers are primarily for household use, while type C breakers are for industrial applications where short circuits are common and wiring is installed accordingly.
Therefore, type C breakers can be used in an EnergyHub installation if accepted by the electrician performing the installation.
We constantly want to improve the content in the Knowledge Database and would appreciate it if you give feedback on our articles. Does all the information exist, is there anything that needs to be clarified or is there any information that is missing that would help installing or using the Ferroamp system in general? You can give us feedback by choosing if the article was helpful or not in the options below.