Can you extend the cable to the current transformers?

*NOTE: The information below is directed towards installers. Only trained electricians are allowed to install Ferroamp’s products.  


Answer:


Yes, the cables for the current transformers can be extended with a twisted pair cable. A pair is required for each current transformer. Total loop resistance should be kept below 10 ohms. The maximum length the cable can have without affecting the measurement accuracy is then given by:


Note that the measurement accuracy can still be affected if long cables run in parallel with other live cables. In such cases, a shielded cable can contribute to reduced crosstalk from the adjacent cables.


We constantly want to improve the content in the Knowledge Database and would appreciate it if you give feedback on our articles. Does all the information exist, is there anything that needs to be clarified or is there any information that is missing that would help installing or using the Ferroamp system in general? You can give us feedback by choosing if the article was helpful or not in the options below. 