What cable should I use between my EnergyHub and the electrical panel in the building?

*NOTE: The information below is directed towards installers. Only trained electricians are allowed to install Ferroamp’s products.  


Answer:


The choice of AC cable for an EnergyHub depends on the size of the EnergyHub being installed and:

  • How much power the EnergyHub will switch
  • How much phase balancing the EnergyHub has available

Full phase balancing means that the maximum current in the neutral conductor can be up to 1.7 times the maximum phase balancing value.



The table below provides an overview of the maximum current that can flow in the neutral conductor and how much the cable must be able to handle (at least). 
 



Example:

So an EnergyHub Wall 14 kW can handle a 5G6 cable maximum power and full phase balancing current for all installation methods as long as the distance to the electrical panel does not exceed about 50 meters. We recommend using flexible cable with multi-stranded conductors to facilitate installation. For example, H07RN-F.

Tools: For more accurate calculations, see Ferroamp's Cable calculator.


We constantly want to improve the content in the Knowledge Database and would appreciate it if you give feedback on our articles. Does all the information exist, is there anything that needs to be clarified or is there any information that is missing that would help installing or using the Ferroamp system in general? You can give us feedback by choosing if the article was helpful or not in the options below. 


If you need to get in contact with Ferroamp's Technical Support or if you have any questions about the system, you can do so by creating a ticket here



Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select atleast one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article