Can I power my EnergyHub with a backup power generator?

Answer:


It is possible to power the EnergyHub with a backup power generator. However, it requires that:


  1. The backup generator must maintain a stable frequency; otherwise, the EnergyHub may trip due to the grid code requirements it adheres to. The maximum frequency change rate (df/dt) is 2 Hz/s. Generally, a larger generator is better so that it does not slow down if a larger load is connected. In previous tests, a 50 kVA generator was used.
  2. Current transformers must be positioned so that generator connections are measured. Simply put: Grid - Generator - Current Transformers - EnergyHub - House loads.
     
  3. The EnergyHub must be configured to disallow any export.



We constantly want to improve the content in the Knowledge Database and would appreciate it if you give feedback on our articles. Does all the information exist, is there anything that needs to be clarified or is there any information that is missing that would help installing or using the EnergyHub system in general? You can give us feedback by choosing if the article was helpful or not in the options below. 