Modified on Tue, 23 Apr 2024 at 01:17 PM

Why does the AC cable to the EnergyHub need to be sized for 1.7 times the phase balancing current?

*NOTE: The information below is directed towards installers. Only trained electricians are allowed to install Ferroamp’s products.  


Answer:


Each EnergyHub has the ability to perform phase balancing to even out imbalances in the power grid. The phase balancing capacity indicates how much current can be transferred between phases.

Because current is transferred between phases in the property's three-phase system to balance out imbalances, it also means that different amounts of current will flow in the neutral conductor of the three-phase system, depending on how much we consume and balance.

At most, there can be 1.7 times as much current in the neutral conductor between the EnergyHub and the property's main electrical panel.


Example:


Read more here.


We constantly want to improve the content in the Knowledge Database and would appreciate it if you give feedback on our articles. Does all the information exist, is there anything that needs to be clarified or is there any information that is missing that would help installing or using the Ferroamp system in general? You can give us feedback by choosing if the article was helpful or not in the options below. 


If you need to get in contact with Ferroamp's Technical Support or if you have any questions about the system, you can do so by creating a ticket here



Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select atleast one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article